SE2607
Structural
- Sep 24, 2010
- 292
Follow along with the video below to see how to install our site as a web app on your home screen.
Note: This feature may not be available in some browsers.
Oops. My bad. It's a W8x15.Pretty sure you're saying a W10x15 is 8 1/8" tall, and I like steel to create torsional stability in the beam (usually an end plate).
I question the ability of the 2 or 3 10dx1-1/2" nails near the end of the beam to meet the requirements of AISC J10.7. But you have the whole picture - if you can conclude that it does the job, then great.but won't the nailer attached to the floor sheathing provide torsional resistance?
No attachment?For me, I would have no attachment to the post and use studs instead of PSL for only 4K. The floor diaphragm will keep it in place.
To be fair, I doubt anything is surviving a 1g acceleration.The Northridge earthquake, not a design level EQ, generated vertical accelerations of greater than 1g.
If the engineers designing don't do their jobs, perhaps....To be fair, I doubt anything is surviving a 1g acceleration.
Where is that, exactly? I've always done it because it makes sense to do it, but nobody has ever been able to point me to a specific place in the code where such a requirement resides, and I've never stumbled across it.How would you comply with the "positive connection" requirement of the code?
I realized that when I wrote the post, but I did it (wrote the post) anyway.Where XR practices, seismic loads will be of very minimal concern.
It's there because I've had a plan check comment. While addressing the comment, I checked the code reference to verify, but I don't recall where it is.Where is that, exactly? I've always done it because it makes sense to do it, but nobody has ever been able to point me to a specific place in the code where such a requirement resides, and I've never stumbled across it.
That's why there was so much damage for an EQ much less than a design level EQ. Northridge is a thrust fault causing predominantly vertical acceleration whereas most of the faults in California are strike slip faults, which are predominantly horizontal.To be fair, I doubt anything is surviving a 1g acceleration.
For vertical accelerations of 1g? Lateral sure.If the engineers designing don't do their jobs, perhaps....
I don't design for 1g vertical. The code requires Ev = 0.2 * 0.7 * SDS, allowable stress design.For vertical accelerations of 1g? Lateral sure.