Continue to Site

Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations cowski on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  • Users: pwrengrds
  • Content: Threads
  • Order by date
  1. pwrengrds

    Capacitor bank neutral voltage

    This is a ungrounded neutral capacitor bank tied to a 34.5kV main power transformer Y grounded. All the A phase fuses blew, not sure why currently. I'm looking at the event and the neutral voltage before the event was 1.2 kV < -178, likely due to voltage imbalance. After the event, before it...
  2. pwrengrds

    Transformer Fan operation

    What are the best practices for settings the fan control temperatures on a 50-100 MVA, 65C rise, ONAN/ONAF/ONAF, mineral oil transformer? What temperatures should the fans be set to operate at? Usually I have seen 65C/75C or 75C/85C. We are in process of startup and the manufacture is...
  3. pwrengrds

    Single phasing delta Y transformers

    This is at a wind farm site where the cables are underground going to multiple padmounts connected in parallel, standard setup. The main power transformer is Wye connected on the 34.5kV side. The collector string is connected delta-Wye. We had a padmount nearest to the substation (connected...
  4. pwrengrds

    8.4kV PT primary operated ungrounded on 13.8kV system

    What is your take on the rating provided. The system is connected to a 13.8kV ungrounded system, the PT's are PTG5-1-110-842F, see attached spec sheet. The PT's are connected phase to ground, the max system voltage rating is 15.5kV. Is the PT with the primary voltage rated at 8400 volts...
  5. pwrengrds

    NERC reporting requirements

    Is a site required to report to NERC if the protection system would not have operated if there was a fault? The equipment is tied to the bulk electrical system that would not have operated if there was a fault, fortunately no fault happened and it was found and corrected (relay programming...
  6. pwrengrds

    Contactor size

    I have a contactor for a synchronous motor that has no nameplate. The current motor field is rated at 75 amps and the contactor has a 100 amp shunt attached. I am being asked if it would support a 150 amp synchronous motor field. Could anyone provide feedback as to the size and rating of the...
  7. pwrengrds

    GE G60 relay loss of excitation

    This isn't a question but something I learned over the past month due to a loss of exciter failure. The generator was being commissioned and the exciter feeder breaker was undersized and tripped, causing a loss of excitation. It did not trip on loss of excitation, but caused some serious...
  8. pwrengrds

    Loss of Excitation

    A 5MVA (rewound to 10MVA), 13.8kV steam turbine generator was operating normally. Some of the control screens started operating oddly and the operators decided to trip it off, so the power was lowered to 0.5MW and the stop valve tripped. It turned out the control screen issues were due to low...
  9. pwrengrds

    TCC curves shifted by total fault current

    I am reviewing a coordination study and all the TCC's and pickup points are shifted by varying amounts. The explanation given is All of the graphs have the curves aligned to the “total fault current”. Have any of you heard of this? Is it a common practice? I haven't and have been doing...
  10. pwrengrds

    Motor current imbalance with balanced voltages

    I was asked to investigate imbalanced currents in a new installation. Location is in rural NW USA, estimated about 7-10 miles from the substation. Loads are mostly motors and lighting, it's a brick plant. There are two buildings, with two services, the transformer (500kVA; 20.5kV/480...
  11. pwrengrds

    Touch shock at 345kV breaker control panel

    I was at a wind park substation (345 kV / 34.5 kV) in the central US (Oklahoma) working on other projects and was asked to look at the main 345 kV breaker control panel. It is grounded to the ground mat (4/0 bare copper), both at the control panel and the breaker frame. When touching the...
  12. pwrengrds

    GE Power Vac Failure

    5kV GE Power Vac 1200 amp breakers are being used for motor starters to start a 1061 amp motor. They have been in service since 1980. We have had two failure in the past couple of months involving the line side stabs failing during motor starts. The stabs are vaporized, the breaker ejected...
  13. pwrengrds

    Tertiary winding CT

    At what transformer size would you normally put in a CT to monitor the current on the tertiary winding of a Y-gnd/buried delta/Y-gnd transformer? I am dealing with wind farm applications, 100-150 MVA, 240kV/34.5kV sized transformers and would like to find some information on how to set them (I...
  14. pwrengrds

    Capacitor banks neutral grounding

    There are three cap banks (7800kVAR, 130 amps, 34.5kV) at a outdoor substation. The 34.5kV is hard neutral grounded at the transformer. They have an neutral unbalance relay that trips them off with an unbalance if the individual caps blow fuses. Each cap bank is grounded through a PT (175/1)...
  15. pwrengrds

    SEL mirrored bits and relay failure

    I am involved in commissioning wind park in Calif. They have two substations about 200 meters apart attached to a 5 mile line going to the 230kV utility grid connection. Sub 2 has been in operation for 2+ years, sub 2 is new. There are two line protection relays in sub 2, CT's in both...
  16. pwrengrds

    Shorting of NGR on over current

    I am working on a relay upgrade of an existing switchgear. (CA,USA) The utility comes in at (fused at 80E) 60kV, and feeds the switchgear at 5kV though a 5MVA Y-Y transformer with a NGR on the secondary. The switchgear has 3 breakers feeding the plant load and a 5MVA generator which also has a...
  17. pwrengrds

    Dry type transformer core overheating (300F)

    There are two idential 550kVA transformers in an industrial plant. Durning a infared scan one core was recorded at 300F. They are 4160 delta/460 delta 220C insulation, 150C rise, dry type transformers. One is at 95% tap, the other at 100% tap. Tests on the transformer (power factor...

Part and Inventory Search