Hi
I have encountered a curious CT connection and need some assistance.
(1)2 CT's one in "a" phase the other in "b" phase.
(2)s1 of the "a" phase CT is connected to s2 of the "b" phase CT.
(3) s2 of the "a" phase CT is connected to s1 of the "b" phase CT
The combined output is used in a OLTC...
High impeadance bus zone protection with 3-ct's connected in parallel for each feeder feeding onto buswires with a high impeadance relay across is what I am use to seeing for this type of protection in metal clad switchgear. The other day whilst on an open conductor site I noticed 2 out of the 3...
Can anyone help explaining this one. A customers has a 1MVA 6.6/0.415Kv Dyn11 transformer
with a solidly earthed neutral. The factory which this transformer supplies has a number
of 3-phase motors supplied from it, a problem occurred on the utility incoming supply
which left only 2-phases...