  1. lrob

    continous and non-continous loads

    I have small piece of industrial type equipment with DC drives, heaters, dc power supply, PLC and servo drive. The motor and heaters all run in cyclic mode. When I calculate my protection current the total load is almost 30 amps of 230vac. When I place a clamp on amp meter and monitor the peak...
  2. lrob

    Transformer sizing with non-continous loading

    I have an application with 208 to 120 transformer single phase needed. I have 4 amps continous load, 2x 8.5 amp non-continous heater load and 7 amp non-continous heater load. The total amp draw is 28 amps. The non-continous is on for no more than 1 minute at start-up, the rest of the time it is...
  3. lrob

    DC field slowly shorting?

    I have a 250 HP dc motor that seems to slowly short the shunt field. The motor is a shunt, series motor. The shunt field had similar problem two years ago. I am looking at application speed. I was also considering if there is something in the Drive that could be out of adjustment and slowly...
  4. lrob

    Sprinkler clearance from ceiling

    In a manufacturing facilty is there a reference for clearance of sprinkler head from ceiling? Is there a min or max distance from ceiling? The facility produces plastic piping
  5. lrob

    Disconnect physical height?

    I have a motor with a fused disconnect. The disconnect is mounted within several feet of the motor. It is in a room that has five other motors. We have disconnects for each motor. The room houses a industrial water filter pool and these are the circulating pump motors. What is the NEC reference...
  6. lrob

    BCD,HEX,BINARY,DECIMAL ??

    I have been programming with A-B and GE. In their programming software they display and manipulate numerical values in a decimal format. I have resently been exposed to programming an Omron CPM2A plc. I have a real problem tracking when the result of an instruction is going to end up with a Hex...
  7. lrob

    Data logging in Excel?

    My functionality in Excel is limited, however Iam currently looking at options for recording data in my plant. I can get real time information to Excel, I just dont know if I can use Excel to histrically save this information into retrievable files?
  8. lrob

    Omron cpm2a pulse instruction

    Iam having trouble learning about the programming for the cpm2a. The pulse instructions are considered expnasion instructions. When I try to download my program I get a download error message that the DIP switch setting or PC setting are not right. I have checked the default settings in the PC...
  9. lrob

    Vacuum control by changing motor speed?

    I posted this in motor and controls forum, then realized this forum is probaly more appropriate. I have a vacuum tank that I currently control vacuum with a proportional valve (with mechnical linkages). I am looking to improve my control. I was wondering if I could control the vacuum by changing...
  10. lrob

    Change motor speed for vacuum control?

    I have a project to improve the control of a vacuum tank in my process. Currently I have a proportional valve that opens and closes based on vacuum setpoint. My question is can I change the speed of the vacuum pump and get the same or better results? I have 3 phase 460V motor.
  11. lrob

    Web Browser to PLC

    I have ocassionally seen reference to user web browsers to monitor PLC information. This also translates to web browsers used as HMI. Do I have a misunderstanding of this, if not what is the basic concept on this and where can I learn more on this subject?
  12. lrob

    GE SNP Identifier

    Iam currently setting up a TCP touchscreen. My system has five 90/30's on a multidrop. The TCP configuration is looking for a 6 digit identifier for the SNP address. If my PLC has a SNP address of 6 what would the 6 digit identifier be? I have tried 000006. Iam waiting on response from my local...
  13. lrob

    GE logicmaster and win2000

    I am wondering if anyone has had any problems running GE' logicmaster 90 on a windows 2000 operating system? I have not run logicamaster on 2000 yet. My company has an old laptop with 2000 on it. I want to give it to my maint. dept. They are familiar with logicmaster. I have no need to buy...
  14. lrob

    Ethernet to PLC communications

    I looking for information on using ethernet to retrieve information directly from my PLC's (GE 9030). I would like to develop my own monitoring HMI. I need to understand the basic addressing structure and how to point to specific location in a PLC. I will either use VB or pull the information...
  15. lrob

    Delta versus WYE for 240 1ph heaters?

    What is the proper way to supply 240v heaters. I need to use a three phase transformer to supply multiple heaters in a production environment. My main concern is the safety factor. What is the difference/advantages between transformers with a Delta or a WYE secondary? Second part of question...