Hi all,
I am looking at a relief valve that has been installed downstream of a high pressure cylinder. The cylinder contains a gas at a pressure of roughly 2400 psig. The cylinder is hooked up to a regulator that lets the pressure down to approximately 100 psig.
We have a relief valve...
Regarding the backpressure correction factor for balanced bellows PSVs in liquid service, Kw:
Has anyone seen values for Kw for backpressure/setpressure ratios greater than 80%?
I have a situation where I have a ratio greater than 80%, but I have never seen Kw values published for this range.
API RP 520 Part II para. 2.2.2 recommends that the total non-recoverable pressure loss between the protected equipment and the pressure relief valve should not exceed 3 percent.
I have a situation where I have a pressure regulator and a high-to-low pipe code break at the regulator. A PSV is...