  1. VEEKRISH

    Hotel Guest Rooms Space Temperature

    Smali1, it is customary to de-couple the Loads - Sensible & Latent. The Fan Coil will cater to just the Sensible Load and the Latent Load would be taken care of by a separate small duct which will bring in Treated Fresh air from a Central Air Handler. This way, you will be able to limit the size...
  2. VEEKRISH

    PRESSURE INDEPENDENT VAV - ISSUES

    Hey Everyone, I encountered a peculiar situation at one of our sites. Using Pressure Independent VAVs with a Centralized Air Handler. Noticed that on a few VAVs, when the AHU is shut-off, the Controller is registering a negative flow on the BMS. In a System with about 35 VAVs, this is happening...
  3. VEEKRISH

    Sea Water for HVAC Cooling?

    Look at using cupro-nickel condensers (shell and tube). Piping could be HDPE. Go below the low tide line. Look at local environmental laws and codes. Filtration. These are some of the key issues. Need to probably look at de-scaling more frequently
  4. VEEKRISH

    AIR VELOCITY CALCULATION

    Walz, what I am looking for is a Formula which I can use at the design stage. Am not looking at measuring at an actual site. Thanks.
  5. VEEKRISH

    AIR VELOCITY CALCULATION

    Thanks, guys.Most Terminal Manufacturers do provide throws to Terminal Velocities of 50-100-150 FPM. I just wanna check if there is a method to evaluate the ditance at which the velocity could be a pre-determined value.
  6. VEEKRISH

    AC Units Linked w/Evaporative Coolers

    The idea would work fine if the RH is low (around 20 ~ 30%) on cooling days with high outdoor DB temps. We do this on Big Chillers here in some parts of India where the summers are dry.The only thing to keep in mind is that the Condensor Fan must be able to overcome the increased static. You...
  7. VEEKRISH

    Occupancy sensor tied to VAV box dual minimum

    Always a good idea to couple a Temp Sensor an CO2 Sensor. Works best based on my experience.
  8. VEEKRISH

    how to design SPUs for an Elevator room?

    Rather than using a thumb rule, I guess it is quicker and safer to do a load calculation. All you need is to factor in the fabric load and the Motor Load. Fresh Air would be Zero. No Occupancy and minimal lighting.
  9. VEEKRISH

    Thermal Insulation and Duct Liner

    I agree. Internal lining is no longer the order of the day considering IAQ ssues. Remember, in most cases only the initial length from the Unit outlet is lined to attenuate he Fan Sound in Duct. This is better addressed using Attenuators. External Insulation is provided to limit rise in...
  10. VEEKRISH

    Question about Sizing HVAC split

    Hi, I assume that the Split Unit would be a DX Coil, and, that the Coil depth will not probably be more than 3 row deep. In your case since he total Enthalpy of the Room is lower than the Unit Capacity, it should do the job, albeit at a slightly elevated DB with lowered RH. You will still be...
  11. VEEKRISH

    AIR VELOCITY CALCULATION

    Hi. Does anybody know of a mathematical method of computing the velocity of air at a specified distance from the Air Outlet ? Application is a Laboratory where we need to maintain a velocity of 20 FPM at the Occupied Zone. Temperature of primary air being supplied will be about 55 deg F...
  12. VEEKRISH

    Dining Room Occupancy

    By ventilation, I presume you are refering to Outside Air. Considering that most public places do not permit smoking, you could tune down the air quantity to 15 CFM per person. In public spaces where occupancy tends to swing between extremes, it is appropriate to use demand based ventilation...
  13. VEEKRISH

    Jet fans for car parks - cost justification

    As I have understood it, the mmajor tangible advantages of the Jet fan system are : (1) No Ducting. (2) Saving in height (from construction point of view) since ducts need not be factored in. The other more significant advantage is - In conventional system you would have a supply air fan and...
  14. VEEKRISH

    AHU Fan Over-Amping

    Assuming that everything else is as per design, and, that the AHU is new, motor is new, installation is proper, then it is very likely that the AHU Pulley may be sized for higher speeds. One easy way to check - if your Return is not ducted, just block the RA side and see if the increased static...
  15. VEEKRISH

    Silence a Return grille

    3 5.0 TR Unit should be delivering around 6,000 CFM. If they are Chilled water Units, then the grille area of 14 sq ft (even accounting for 50 % free area) should leave you with a Extract Air Velocity of about 850 FPM - good enough and should not create a noise issue. Probably the noise is from...
  16. VEEKRISH

    Air compressor room exhaust

    150 HP, with both the motor and driven machine in the space would mean you are looking at about 420,000 BTUs oer hour. So even if we are looking at all outside air and want to mainatain a differential with outside of 20 deg F, then we will be looking at about 19,500 CFM. For a room of this size...
  17. VEEKRISH

    Commissioning of dampers

    For Fire Dampers, Fire & Smoke Dampers and Smoke Dampers, what is important is that all installation recommendations are taken care of (NFPA 90 guidelines, for example). For Fire Dampers with Fusible Link, insist on UL Certified Fusible Links. For Dampers with actuators, use a Control Panel...
  18. VEEKRISH

    garage ventilation

    Axial Flow Fans are OK, but how about the noise ? That is a serious disadvantage. If the area is not too large, just look at some simple propeller fans (wall mounted) which when located properly will do the job admirably at fairly low noise levels. All would depend upon your layout, area etc. If...
  19. VEEKRISH

    Ventilation of Hazardous Area

    I go with ChasBean1. Any hazardous area will mandate negative pressure with respect to the surroundings for containment. I will sya, go with 10% less make up as compared to extract air. That should do the trick.
  20. VEEKRISH

    heat load calculation for residential jobs.

    Have you tried the E20 from Carrier ?