I don´t advice that you could make process vacuum only to 10 % of active parts(pappers, isolaters), remenber that furanos test is for aging of papper, you need to makea good process vacuum to all active part,after that dew point test
finally fill up the oil under vacuum then Power factor test...
Each manufacter has his own spewcification, upon Circuit Breakers , GIS and insulated equipments must be carried out HV test on site.for example for a equipment of 145 KV be aplied 235 KV x 1min
partial discharge measurements-> o,5 pc
but IEC could accept some peaks until 10 PC.